DataLink Product Selection Chart:
Use the following chart to
help choose what DL product works best in your application.

DH485 is a local area network (LAN) designed
for factory-floor applications. DH-485 allows for connection up to 32
devices, including SLC 500 and MicroLogix 1000 controllers, color graphics
systems, and personal computers. The DH485 link together with auxiliary
RS-232-C (DF1 protocol) links make up the DH-485 network. With RSLinx
software installed on a PC, communication with other nodes on the network
is possible. Using SLC 500 Programming Software, program SLC 500 controllers
over the DH485 network. This means that a single PC connected to the
network can be used to program all the SLC 500 controllers on the network.
Options on each interface allow for easy reconfiguration of the network
when it changes.

Specifications
- Cable type: Belden 3106A
- Trunkline length: 4000 ft max.
- Transmission rate: 19.2 kbit/s max.
- Medium access method: token passing
Typical Configuration